KS700 Operating Features - Other
CFR(s): NFPA 101

Operating Features - Other List in the REMARKS section any LSC Section 32.7 and 33.7 Operating Features requirements that are not addressed by the provided K-tags, but are deficient. This information, along with the applicable Life Safety Code or NFPA standard citation, should be included on Form CMS-2567.


This STANDARD is not met as evidenced by:
Based on review of documentation, the facility failed to maintain the testing of the diesel generator per the requirements of:

2012 NFPA 99, 6.5.4.1.1.2, 6.4.4.1.1.3, and 6.5.4.2

2010 NFPA 110, 1.3, 8.4.2, 8.4.2.3, and 8.3.8

This deficiency affects 1 of 1 generator.

Findings include:

During a tour of the facility, the facility failed to provide documentation on the following:

1. Testing the diesel generator:

i. Once monthly for a minimum of 30 minutes under one of the following conditions:

a. Operating temperature conditions at not less than 30% of the nameplate kW

rating

b. Loading that maintains the minimum exhaust gas temperature

OR

ii. Provide an annual 1.5-hour supplemental load test at not less than 50% of the EPS nameplate kW rating
for 30 continuous minutes and at not less 75% of the EPS nameplate KW rating for one continuous hour for
a total test duration of not less than 1.5 continuous hours.

2. To have a fuel quality test performed at least annually using tests approved by ASTM standards.

A member of the maintenance staff was present when this deficiency was identified.