KS351 Sprinkler System - Installation
CFR(s): NFPA 101

Sprinkler System - Installation Where an automatic sprinkler system is installed, for either total or partial building coverage, the system shall be in accordance with Section 9.7 and shall initiate the fire alarm system in accordance with Section 9.6, as modified below. The adequacy of the water supply shall be documented. In Prompt Evacuation facilities, an automatic sprinkler system in accordance with NFPA 13D, Standard for the Installation of Sprinkler Systems in One and two Family Dwellings and Manufactured Homes, shall be permitted. Automatic sprinklers shall not be required in closets not exceeding 24 square feet and in bathrooms not exceeding 55 square feet, provided that such spaces are finished with lath and plaster or materials providing a 15-minute thermal barrier. In Prompt Evacuation Capability facilities where an automatic sprinkler system is in accordance with NFPA 13, Standard for the Installation of Sprinkler Systems, automatic sprinklers shall not be required in closets not exceeding 24 square feet and in bathrooms not exceeding 55 square feet, provided that such spaces are finished with lath and plaster or material providing a 15-minute thermal barrier. In Prompt Evacuation Capability facilities in buildings four or fewer stories above grade plane, systems in accordance with NFPA 13R, Standard for the Installation of Sprinkler Systems in Residential Occupancies up to and including Four Stories in Height, shall be permitted. Initiation of the fire alarm system shall not be required for existing installations in accordance with 33.2.3.5.6. Where an automatic sprinkler is installed, attics used for living purposes, storage, or fuel-fired equipment are sprinkler protected by July 5, 2019. Attics not used for living purposes, storage, or fuel-fired equipment meet one of the following: 1. Protected by heat detection system to activate the fire alarm system according to 9.6. 2. Protected by automatic sprinkler system according to 9.7. 3. Constructed of noncombustible or limited-combustible construction; or 4. Constructed of fire-retardant-treated wood according to NFPA 703. 33.2.3.5.3, 33.2.3.5.3.1, 33.2.3.5.3.3, 33.2.3.5.3.4, 33.2.3.5.3.6, 33.2.3.5.7


This STANDARD is not met as evidenced by:
Based on observation, the facility failed to post a list of sprinklers installed in the property at the sprinkler cabinet per the requirements of:

2012 NFPA 101, 33.2.3.5.3, and 9.7

2010 NFPA 13, 6.2.9.7, and 6.2.9.7.1

This deficiency affects the complete sprinkler system.

Findings include:

During a tour of the facility, the surveyor observed the facility failed to post a list of sprinklers installed in the property at the sprinkler cabinet. The list shall include the following:

(1) Sprinkler identification number; or the manufacturer, model, orifice, deflector type, thermal sensitivity, and pressure rating

(2) General description

(3) Quantity of each type to be contained in the cabinet

(4) Issue or revision date of the list

A member of the maintenance staff was present when this deficiency was identified.