KS100 General Requirements - Other
CFR(s): NFPA 101

General Requirements - Other 2012 EXISTING List in the REMARKS section any LSC Section 33.1 or 33.2 General Requirements that are not addressed by the provided K-tags, but are deficient. This information, along with the applicable Life Safety Code or NFPA standard citation, should be included on Form CMS-2567.


This STANDARD is not met as evidenced by:
Based on observation, the facility failed to maintain the oxygen cylinders per the requirements of:

2012 NFPA 99, 11.6.2.3 (11), 11.3.4.1, and 11.6.5.2

This deficiency affects 1 of 1 oxygen storage areas.

Findings include:

During a tour of the facility, the surveyor observed the following in the Med Gas Storage Closet at the Nurses' Station:

1. One 24 cu.ft. and two 6 cu.ft. unsecured oxygen cylinders

2. The door to the closet did not have a precautionary sign that reads:

"Caution:

Oxidizing Gas(es) Stored Within

No Smoking"

3. The empty cylinders were not segregated from the full cylinders

A member of the maintenance staff was present when this deficiency was identified.