Department of Health & Human Services

Centers for Medicare & Medicaid Services
Form Approved

OMB No. 0938-0391

Statement of Deficiencies (X1) Provider/Supplier/CLIA Identification Number 01G011 (X3) Date Survey Completed 03/25/2021
Name of Provider or Supplier Rainbow Omega, Inc, Street Address, City, State 202 Hope Drive, Eastaboga, AL
For information on the provider's plan to correct this deficiency, please contact the provider or the state survey agency.
(X4) ID Prefix Tag Summary Statement of Deficiencies

(Each deficiency should be preceded by full regulatory or LSC identifying information)
K0000 K3 Building: 0101

K6 Plan Approval: 2006

K7 Survey Under: 2012 Existing

K8 ICF/IID Small

Generator: One Diesel, Katolight 125 kW (installed 2007)

FACP: Simplex 4010 (installed 2007)

Locking Devices: None

Smoke Detection: Corridor

Beds: 16

Census:16

Type of Structure: 2006 one story unprotected wood frame, Type V(000). The facility has a complete automatic sprinkler system with a sprinkler pit. The facility is surveyed under impractical to evacuate.

During a routine recertification survey conducted on this date, the facility was found to be not in compliance with 42 CFR 483.470 - ICF/IID as evidenced by the the following deficiencies of the 2012 NFPA 101 Life Safety Code (LSC), the 2012 NFPA 99 Health Care Facilities Code and the standards referenced by these codes, as observed by the LSC Surveyor while accompanied by facility personnel.