Department of Health & Human Services

Centers for Medicare & Medicaid Services
Form Approved

OMB No. 0938-0391

Statement of Deficiencies (X1) Provider/Supplier/CLIA Identification Number 01G011 (X3) Date Survey Completed 06/20/2019
Name of Provider or Supplier Rainbow Omega, Inc, Street Address, City, State 202 Hope Drive, Eastaboga, AL
For information on the provider's plan to correct this deficiency, please contact the provider or the state survey agency.
(X4) ID Prefix Tag Summary Statement of Deficiencies

(Each deficiency should be preceded by full regulatory or LSC identifying information)
KS500 Building Services - Other
CFR(s): NFPA 101

Building Services - Other List in the REMARKS section any LSC Section 32.2.5 and 33.2.5 Building Services that are not addressed by the provided K-tags, but are deficient. This information, along with the applicable Life Safety Code or NFPA standard citation, should be included on Form CMS-2567.


This STANDARD is not met as evidenced by:
Based on review of documentation and interview, the facility failed to maintain the diesel generator fuel per the requirements of:

2012 NFPA 101, 33.2.5, and 9.1.3.1

2010 NFPA 110, 1.3, and 8.3.8

Findings include:

On 06/20/2019, during a tour of the facility from 9:00 am to 12:00 pm, the facility failed to provide documentation that a fuel quality test was performed within the past twelve months using tests approved by ASTM standards.

A member of the maintenance staff was present when this deficiency was found.