| Statement of Deficiencies | (X1) Provider/Supplier/CLIA Identification Number 713026 | (X3) Date Survey Completed 04/27/2026 |
| Name of Provider or Supplier Bogalusa Rehabilitation Hospital | Street Address, City, State 621 Columbia Street, Bogalusa, LA | |
| For information on the provider's plan to correct this deficiency, please contact the provider or the state survey agency. | ||
| (X4) ID Prefix Tag | Summary Statement of Deficiencies
(Each deficiency should be preceded by full regulatory or LSC identifying information) |
| K0345 | Fire Alarm System - Testing and Maintenance CFR(s): NFPA 101 Fire Alarm System - Testing and Maintenance A fire alarm system is tested and maintained in accordance with an approved program complying with the requirements of NFPA 70, National Electric Code, and NFPA 72, National Fire Alarm and Signaling Code. Records of system acceptance, maintenance and testing are readily available. 9.6.1.3, 9.6.1.5, NFPA 70, NFPA 72 This STANDARD is not met as evidenced by: Based on visual observation the facility failed to assure that the fire alarm system was inspected and tested in accordance with the approved maintenance and testing program in NFPA 72. The fire alarm system gives a sense of security to offer an advance warning in fire and/or smoke emergency. This deficient practice could potentially affect ten of ten patients. Findings: During the facility tour on April 27, 2026 between the hours of 9:15 a.m. to 11:00 a.m. the fire alarm system sensitivity test documentation was lacking at time of survey. The interview with Administrator revealed the facility was not aware that the required inspections had not been conducted on the fire alarm system and was acknowledged by the Administrator. |