| Statement of Deficiencies | (X1) Provider/Supplier/CLIA Identification Number 670067 | (X3) Date Survey Completed 04/24/2013 |
| Name of Provider or Supplier Baylor Scott And White Orthopedic And Spine Hospi | Street Address, City, State 707 Highlander Blvd, Arlington, TX | |
| For information on the provider's plan to correct this deficiency, please contact the provider or the state survey agency. | ||
| (X4) ID Prefix Tag | Summary Statement of Deficiencies
(Each deficiency should be preceded by full regulatory or LSC identifying information) |
| K0106 | LIFE SAFETY CODE STANDARD CFR(s): NFPA 101 Hospitals, and nursing homes and hospices with life support equipment, have a Type I Essential Electrical System powered by a generator with a transfer switch and separate power supply. The EES is in accordance with NFPA 99, 3.4.2.2, 3.4.2.1.4. This STANDARD is not met as evidenced by: Facility failed to maintain essential electrical system in accordance with the Standard for Health Care, NFPA (National Fire Protection Association) 99. Findings included the following: Surveyor observed between 11 and 11:30 am on 4/24/13 that electrical room containing switch gear did not have task battery lighting in accordance with NFPA 99: 3-4.2.2.2. |