| Statement of Deficiencies | (X1) Provider/Supplier/CLIA Identification Number 531311 | (X3) Date Survey Completed 10/05/2016 |
| Name of Provider or Supplier Crook County Hospital | Street Address, City, State 713 Oak Street, Sundance, WY | |
| For information on the provider's plan to correct this deficiency, please contact the provider or the state survey agency. | ||
| (X4) ID Prefix Tag | Summary Statement of Deficiencies
(Each deficiency should be preceded by full regulatory or LSC identifying information) |
| K0038 | LIFE SAFETY CODE STANDARD CFR(s): NFPA 101 Exit access is arranged so that exits are readily accessible at all times in accordance with section 7.1. 19.2.1 This STANDARD is not met as evidenced by: . Based on observation and staff interview, the facility failed to arrange exit access so that exits are readily accessible at all times. The findings were: 1. Observation on 10/05/2016 from 8:36 AM to 10:20 AM located in the Maintenance Office (Main level), IT Room, Boiler room, and throughout the facility revealed door locks that required tight pinching, and more than one releasing operation to make the door operable. Interview with the Facility Maintenance Manager at the time of the observation acknowledged the door lock required more than one operation to open. 2. Observation on 10/05/2016 at 8:46 AM located at the Back 40 Storage room revealed a door labeled exit (Door opened into exit stairwell) that was locked and required a key to open. Further observation revealed that limited staff had the key to the exit door. Interview with the Facility Maintenance Manager at the time of observation acknowledged the door was locked against egress and that only a select few had the keys. Ref: 2000 NFPA 101, Sections 19.2.2.2.1 and 7.2.1.5.4 |