Statement of Deficiencies (X1) Provider/Supplier/CLIA Identification Number 531311 (X3) Date Survey Completed 11/15/2011
Name of Provider or Supplier Crook County Hospital Street Address, City, State 713 Oak Street, Sundance, WY
For information on the provider's plan to correct this deficiency, please contact the provider or the state survey agency.
(X4) ID Prefix Tag Summary Statement of Deficiencies

(Each deficiency should be preceded by full regulatory or LSC identifying information)
K0211 LIFE SAFETY CODE STANDARD
CFR(s): NFPA 101

Where Alcohol Based Hand Rub (ABHR) dispensers are installed in a corridor: o The corridor is at least 6 feet wide o The maximum individual fluid dispenser capacity shall be 1.2 liters (2 liters in suites of rooms) o The dispensers have a minimum spacing of 4 ft from each other o Not more than 10 gallons are used in a single smoke compartment outside a storage cabinet. o Dispensers are not installed over or adjacent to an ignition source. o If the floor is carpeted, the building is fully sprinklered. 19.3.2.7, CFR 403.744, 418.100, 460.72, 482.41, 483.70, 483.623, 485.623


This STANDARD is not met as evidenced by:
Based on observation and staff interview, the facility failed to ensure an alcohol based hand rub (ABHR) dispenser was not installed over an ignition source in 1 of 4 smoke compartments. The findings were: Observation on 11/15/11 at 9:48 AM revealed one ABHR dispenser was attached to the wall directly over a light switch in the outpatient entrance. Interview with the maintenance manager at the time of the observation confirmed the dispenser was located over a possible ignition source. Reference: NFPA 101, Life Safety Code, 2000 edition, Section 19.3.2.7. CFR 403.744.