Statement of Deficiencies (X1) Provider/Supplier/CLIA Identification Number 010007 (X3) Date Survey Completed 12/12/2024
Name of Provider or Supplier Mizell Memorial Hospital Street Address, City, State 702 N Main St, Opp, AL
For information on the provider's plan to correct this deficiency, please contact the provider or the state survey agency.
(X4) ID Prefix Tag Summary Statement of Deficiencies

(Each deficiency should be preceded by full regulatory or LSC identifying information)
K0362 Corridors - Construction of Walls
CFR(s): NFPA 101

Corridors - Construction of Walls 2012 EXISTING Corridors are separated from use areas by walls constructed with at least 1/2-hour fire resistance rating. In fully sprinklered smoke compartments, partitions are only required to resist the transfer of smoke. In nonsprinklered buildings, walls extend to the underside of the floor or roof deck above the ceiling. Corridor walls may terminate at the underside of ceilings where specifically permitted by Code. Fixed fire window assemblies in corridor walls are in accordance with Section 8.3, but in sprinklered compartments there are no restrictions in area or fire resistance of glass or frames. If the walls have a fire resistance rating, give the rating _____________ if the walls terminate at the underside of the ceiling, give brief description in REMARKS, describing the ceiling throughout the floor area. 19.3.6.2, 19.3.6.2.7


This STANDARD is not met as evidenced by:
. Based on observation, the facility failed to provide ceilings required for the pendant sprinklers in the facility per the requirements of: 2012 NFPA 101, 19.3.6.2.4 This deficiency affects Laundry Room only . Findings include: During a tour of the facility, the surveyor observed four, 2' x 4' ceiling tiles missing in the folding area of Laundry Room. A member of the maintenance staff was present when this deficiency was identified. .