| Statement of Deficiencies | (X1) Provider/Supplier/CLIA Identification Number 010007 | (X3) Date Survey Completed 12/12/2024 |
| Name of Provider or Supplier Mizell Memorial Hospital | Street Address, City, State 702 N Main St, Opp, AL | |
| For information on the provider's plan to correct this deficiency, please contact the provider or the state survey agency. | ||
| (X4) ID Prefix Tag | Summary Statement of Deficiencies
(Each deficiency should be preceded by full regulatory or LSC identifying information) |
| K0133 | Multiple Occupancies - Construction Type CFR(s): NFPA 101 Multiple Occupancies - Construction Type Where separated occupancies are in accordance with 18/19.1.3.2 or 18/19.1.3.4, the most stringent construction type is provided throughout the building, unless a 2-hour separation is provided in accordance with 8.2.1.3, in which case the construction type is determined as follows: * The construction type and supporting construction of the health care occupancy is based on the story in which it is located in the building in accordance with 18/19.1.6 and Tables 18/19.1.6.1 * The construction type of the areas of the building enclosing the other occupancies shall be based on the applicable occupancy chapters. 18.1.3.5, 19.1.3.5, 8.2.1.3 This STANDARD is not met as evidenced by: . Based on observation, the facility failed to maintain the separation between construction types per the requirements of: 2012 NFPA 101, 19.1.3.5, and 8.2.1.3 (1) This deficiency affects the only 2-hour fire barrier in this building. Findings include: During a tour of the facility, the surveyor observed the door between the Kitchen and Dining Room, in the 2-hour fire barrier separating Building 0103 and Building 0203, had a self-closing device but was propped open with a wood wedge and would not self-close in and emergency. A member of the maintenance staff was present when this deficiency was identified. . |