K0353 Sprinkler System - Maintenance and Testing
CFR(s): NFPA 101

Sprinkler System - Maintenance and Testing Automatic sprinkler and standpipe systems are inspected, tested, and maintained in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintaining of Water-based Fire Protection Systems. Records of system design, maintenance, inspection and testing are maintained in a secure location and readily available. a) Date sprinkler system last checked _____________________ b) Who provided system test ____________________________ c) Water system supply source __________________________ Provide in REMARKS information on coverage for any non-required or partial automatic sprinkler system. 9.7.5, 9.7.7, 9.7.8, and NFPA 25


This STANDARD is not met as evidenced by:
. Based on review of documentation and interview, the facility failed to provide documentation on the testing and inspection of the automatic sprinkler system per requirements of: 2012 NFPA 101, 4.6.12.3, 4.6.12.4, 9.7.5, and 9.7.7 2011 NFPA 25, Table 5.1.1.2, 5.2.4.1, 5.3.4, and TIAs 11-1, 11-2, 11-3 and 11-4 This deficiency could affect all occupants. On 04/11/2019, during a tour of the facility from 8:00 am to 12:30 pm, the facility failed to provide the following documentation : 1. The monthly inspections on the wet sprinkler riser gauges 2. The quarterly automatic sprinkler inspection records for the past 12 months. Only one report dated 02/20/2019 was provided for review. The service tags on the riser indicated 08/2018, 08/17, 09/16, 02/16 as dates the system was inspected. A member of the maintenance staff was present when the deficiency was found. .