Statement of Deficiencies (X1) Provider/Supplier/CLIA Identification Number 010006 (X3) Date Survey Completed 07/15/2010
Name of Provider or Supplier North Alabama Medical Center Street Address, City, State 1701 Veterans Drive, Florence, AL
For information on the provider's plan to correct this deficiency, please contact the provider or the state survey agency.
(X4) ID Prefix Tag Summary Statement of Deficiencies

(Each deficiency should be preceded by full regulatory or LSC identifying information)
K0054 LIFE SAFETY CODE STANDARD
CFR(s): NFPA 101

All required smoke detectors, including those activating door hold-open devices, are approved, maintained, inspected and tested in accordance with the manufacturer's specifications. 9.6.1.3


This STANDARD is not met as evidenced by:
The facility failed to perform sensitivity testing of the smoke detectors. Findings include: Documentation provided by the facility during the survey did not indicate sensitivity testing of the smoke detectors. Detector sensitivity shall be checked with one year after installation and every alternate year thereafter per 72, 7-3.2.1. (Up to 5 years permitted under certain circumstances. See 7-3.2.1).