| (X4) ID Prefix Tag | Summary Statement of Deficiencies
(Each deficiency should be preceded by full regulatory or LSC identifying information) |
| K0325 | Alcohol Based Hand Rub Dispenser (ABHR) CFR(s): NFPA 101 Alcohol Based Hand Rub Dispenser (ABHR) ABHRs are protected in accordance with 8.7.3.1, unless all conditions are met: * Corridor is at least 6 feet wide * Maximum individual dispenser capacity is 0.32 gallons (0.53 gallons in suites) of fluid and 18 ounces of Level 1 aerosols * Dispensers shall have a minimum of 4-foot horizontal spacing * Not more than an aggregate of 10 gallons of fluid or 135 ounces aerosol are used in a single smoke compartment outside a storage cabinet, excluding one individual dispenser per room * Storage in a single smoke compartment greater than 5 gallons complies with NFPA 30 * Dispensers are not installed within 1 inch of an ignition source * Dispensers over carpeted floors are in sprinklered smoke compartments * ABHR does not exceed 95 percent alcohol * Operation of the dispenser shall comply with Section 18.3.2.6(11) or 19.3.2.6(11) * ABHR is protected against inappropriate access 18.3.2.6, 19.3.2.6, 42 CFR Parts 403, 418, 460, 482, 483, and 485 This STANDARD is not met as evidenced by: . Based on observation and interview, the building failed to maintain the Alcohol Based Hand Rub Dispensers (ABHRs) per the requirements of: 2012 NFPA 101, 19.3.2.6* (8) and (11) (f) Findings include: 1. On 10/03/2017, during a tour of the building from 8:00 am to 4:15 pm, the Alcohol Based Hand Rub Dispensers on the First Floor in the H & V Suite/CDU were observed installed above a light switch (ignition source) at the following locations: a. Room 1133 b. Room 1134 c. Room 1138 d. Room 1142 e. Room 1147 f. At the Nurses' Station 2. On 10/04/2017, during review of documentation from 8:00 am to 5:00 pm, the building failed to provide documentation on policy and procedure on testing in accordance with the manufacturer's care and use instructions each time a new refill is installed. ROLAND 3. On 10/02/2017, during a tour of the building from 10:30 am to 5:45 pm, an ABHR was observed mounted directly above a Nurses' Call Switch (ignition source) on the 7th Floor near the Nurses' Station. 36148 4. On 10/03/2017, during a tour of the building from 8:00 am to 4:15 pm, an Alcohol Based Hand Rub Dispenser in the GI Lab Room #1 located in the Basement was observed installed above a light switch (ignition source). A member of the maintenance staff was present when this deficiency was identified. . |