| Statement of Deficiencies | (X1) Provider/Supplier/CLIA Identification Number 010001 | (X3) Date Survey Completed 10/05/2017 |
| Name of Provider or Supplier Southeast Health Medical Center | Street Address, City, State 1108 Ross Clark Circle, Dothan, AL | |
| For information on the provider's plan to correct this deficiency, please contact the provider or the state survey agency. | ||
| (X4) ID Prefix Tag | Summary Statement of Deficiencies
(Each deficiency should be preceded by full regulatory or LSC identifying information) |
| K0232 | Aisle, Corridor, or Ramp Width CFR(s): NFPA 101 Aisle, Corridor or Ramp Width 2012 EXISTING The width of aisles or corridors (clear or unobstructed) serving as exit access shall be at least 4 feet and maintained to provide the convenient removal of nonambulatory patients on stretchers, except as modified by 19.2.3.4, exceptions 1-5. 19.2.3.4, 19.2.3.5 This STANDARD is not met as evidenced by: . Based on observation and interview, the building failed to maintain the corridors per the requirements of: 2012 NFPA 101, 19.2.3.4 (5) (a) and (c) Findings include: On 10/02/2017, during a tour of the building from 10:30 am to 5:45 pm, the facility failed to maintain the Fourth Floor corridors: 1. In the 8'-0" corridors unsecured furniture was observed in the following locations: a. In the connector wing at room 470 b. At elevator B1 2. The furniture at elevator B1 was observed to be on both sides of the 8'-0" corridor. A member of the maintenance staff was present when this deficiency was identified. . |