K0918 Electrical Systems - Essential Electric Syste
CFR(s): NFPA 101

Electrical Systems - Essential Electric System Maintenance and Testing The generator or other alternate power source and associated equipment is capable of supplying service within 10 seconds. If the 10-second criterion is not met during the monthly test, a process shall be provided to annually confirm this capability for the life safety and critical branches. Maintenance and testing of the generator and transfer switches are performed in accordance with NFPA 110. Generator sets are inspected weekly, exercised under load 30 minutes 12 times a year in 20-40 day intervals, and exercised once every 36 months for four continuous hours. Scheduled test under load conditions include a complete simulated cold start and automatic or manual transfer of all EES loads, and are conducted by competent personnel. Maintenance and testing of stored energy power sources (Type 3 EES) are in accordance with NFPA 111. Main and feeder circuit breakers are inspected annually, and a program for periodically exercising the components is established according to manufacturer requirements. Written records of maintenance and testing are maintained and readily available. EES electrical panels and circuits are marked and readily identifiable. Minimizing the possibility of damage of the emergency power source is a design consideration for new installations. 6.4.4, 6.5.4, 6.6.4 (NFPA 99), NFPA 110, NFPA 111, 700.10 (NFPA 70)


This STANDARD is not met as evidenced by:
. Based on observation and review of documentation, the facility failed to maintain the testing of the diesel emergency generator per the requirements of: 2012 NFPA 101, 21.2.9.1, and 7.9.2.4, 2010 NFPA 110, 8.3.7.1, 5.6.5.6, 5.6.5.6.1, 1.3, and 8.3.8 This deficiency affects the whole facility. Findings include: On 04/05/2023, during a tour of the facility from 8:30 am to 10:30 am, the facility failed to provide the following: 1. Documentation of performing monthly conductance testing on the facility's emergency generator maintenance-free batteries for the past 12 months. 2. Documentation that a fuel quality test was performed within the past twelve months using tests approved by ASTM standards. A member of the maintenance staff was present when this deficiency was identified.