| Statement of Deficiencies | (X1) Provider/Supplier/CLIA Identification Number 034525 | (X3) Date Survey Completed 08/07/2018 |
| Name of Provider or Supplier Saguaro Rehabilitation And Aquatic Therapy, Llc | Street Address, City, State 305 North Plaza Drive, Apache Junction, AZ | |
| For information on the provider's plan to correct this deficiency, please contact the provider or the state survey agency. | ||
| (X4) ID Prefix Tag | Summary Statement of Deficiencies
(Each deficiency should be preceded by full regulatory or LSC identifying information) |
| I0585 | MAINTENANCE CFR(s): 485.62(c)(1) The facility must establish a written preventive maintenance program to ensure that all equipment is properly maintained and equipment needing periodic calibration is calibrated consistent with the manufacturer's recommendations. This STANDARD is not met as evidenced by: Based on observations during tour, review of policies and procedures, manufacturer recommendations documents, and staff interviews, it was determined that the facility failed to follow manufacturer recommendations to ensure that the facility hydrocollator equipment was drained and cleaned every two weeks as per manufacturer's recommendations. This deficient practice poses the high potential risk for the spread of infection and cross contamination between patients, which will affect patient safety, Findings Include: The surveyors observed during a observation on tour conducted on 08/01/18, a [brand name] hydrocollator in use. Review of the online Hydrocollator Heating Units Service and User Manual - Chattanooga Group (http://www.ersbiomedical.com/Manuals/chatt/Hydroc_svc_manu.pdf) recommended: "...1. Maintain 1 of 1 hydrocollator: Regularly clean and drain the tank (every two weeks)...." The surveyors requested the facility copy of the manufacturer recommendations for maintenance and care of the hydrocollator ? No manufacturer recommendations were provided. for the Facility document titled "Daily Temperature Record" revealed the following: Heading "Equipment Name" Hydrocollator. Documentation showed that the hydrocollator was cleaned the following dates: 3/27/17 and 12/19/17 Surveyors requested documentation for the maintenance of the hydrocollator. The facility failed to document the draining of the hydrocollator tank every two weeks. Physical Therapist Aide indicated during an interview conducted on 08/01/18, that s/he thought the hydroculator had to be drained once a month, and confirmed that the facility did not have the manufacturer's manual for reference. |