Statement of Deficiencies (X1) Provider/Supplier/CLIA Identification Number 65C0001001 (X3) Date Survey Completed 02/08/2019
Name of Provider or Supplier Hafa Adai Specialist Group, Llp Street Address, City, State Sunflower Villa, 280 Pale San Vitores, Tamuning, GU
For information on the provider's plan to correct this deficiency, please contact the provider or the state survey agency.
(X4) ID Prefix Tag Summary Statement of Deficiencies

(Each deficiency should be preceded by full regulatory or LSC identifying information)
K0914 Electrical Systems - Maintenance and Testing
CFR(s): NFPA 101

Electrical Systems - Maintenance and Testing Hospital-grade receptacles at patient bed locations and where deep sedation or general anesthesia is administered, are tested after initial installation, replacement or servicing. Additional testing is performed at intervals defined by documented performance data. Receptacles not listed as hospital-grade at these locations are tested at intervals not exceeding 12 months. Line isolation monitors (LIM), if installed, are tested at intervals of less than or equal to 1 month by actuating the LIM test switch per 6.3.2.6.3.6, which activates both visual and audible alarm. For, LIM circuits with automated self-testing, this manual test is performed at intervals less than or equal to 12 months. LIM circuits are tested per 6.3.3.3.2 after any repair or renovation to the electric distribution system. Records are maintained of required tests and associated repairs or modifications, containing date, room or area tested, and results. 6.3.4 (NFPA 99)


This STANDARD is not met as evidenced by:
Based on an interview the facility has failed to test, on an annual basis, receptacles at patient bed locations or in locations where general anesthesia is administered. Failure to do so could increase the risk of medical equipment failing to operate as intended during surgery. This could cause injury or death.



Findings include:



On February 8, 2019 while requesting records related to receptacle testing the office manager and the maintenance employee said that no such testing had been performed in the operating room or the recovery room. This could affect all patients.