Statement of Deficiencies (X1) Provider/Supplier/CLIA Identification Number 55C0001059 (X3) Date Survey Completed 05/12/2026
Name of Provider or Supplier Fort Sutter Surgery Center, A Ca Limited Partnership Street Address, City, State 2801 K Street, Suite 525, Sacramento, CA
For information on the provider's plan to correct this deficiency, please contact the provider or the state survey agency.
(X4) ID Prefix Tag Summary Statement of Deficiencies

(Each deficiency should be preceded by full regulatory or LSC identifying information)
K0521 HVAC
CFR(s): NFPA 101

HVAC Heating, ventilation, and air conditioning shall comply with 9.2 and shall be installed in accordance with the manufacturer's specifications. 20.5.2.1, 21.5.2.1, 9.2


This STANDARD is not met as evidenced by:
Based on record review and interview, the facility failed to maintain the Heating, Ventilating, and Air-Conditioning (HVAC) system. This was evidenced by the failure to provide a current smoke/fire damper testing and service report. This affected all patients and could result in the spread of smoke and/or fire to other locations of the facility due to a malfunctioning damper.

NFPA 101, Life Safety Code, 2012 Edition
21.5 Building Services.
21.5.1 Utilities.21.5.1.1 Utilities shall comply with the provisions of Section 9.1.
21.5.2 Heating, Ventilating, and Air-Conditioning.
21.5.2.1 Heating, ventilating, and air-conditioning shall comply with the provisions of Section 9.2 and shall be installed in accordance with the manufacturer ' s specifications, unless otherwise modified by 20.5.2.2.
9.2 Heating, Ventilating, and Air-Conditioning.
9.2.1 Air-Conditioning, Heating, Ventilating Ductwork, and Related Equipment. Air-conditioning, heating, ventilating ductwork, and related equipment shall be in accordance with NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems, or NFPA 90B, Standard for the Installation of Warm Air Heating and Air-Conditioning Systems, as applicable, unless such installations are approved existing installations, which shall be permitted to be continued in service.

NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems, 2012 edition.
5.4.8 Maintenance.
5.4.8.1 Fire dampers and ceiling dampers shall be maintained in accordance with NFPA 80, Standard for Fire Doors and Other Opening Protective's.

NFPA 80, Standard for Fire Doors and Other Opening Protective's, 2010 edition.
19.3.4 Documentation. All inspections and testing shall be documented, indicating the location of the fire damper, date(s) of inspection, name of inspector, and deficiencies discovered. The documentation shall have a space to indicate when and how the deficiencies were corrected.
19.4* Periodic Inspection and Testing.
19.4.1 Each damper shall be tested and inspected 1 year after installation.
19.4.1.1 The test and inspection frequency shall then be every 4 years, except in hospitals, where the frequency shall be every 6 years.
19.4.4 If the damper is equipped with a fusible link, the link shall be removed for testing to ensure full closure and lock-in place if so equipped.
19.4.5 The operational test of the damper shall verify that there is no damper interference due to rusted, bent, misaligned, or damaged frame or blades, or defective hinges or other moving parts.
19.4.7 The damper shall not be blocked from closure in any way.
19.4.8 The fusible link shall be reinstalled after testing is complete.
19.4.8.1 If the link is damaged or painted, it shall be replaced with a link of the same size, temperature, and load rating.
19.4.9 All inspections and testing shall be documented, indicating the location of the fire damper or combination fire/smoke damper, date of inspection, name of inspector, and deficiencies discovered.
19.4.9.1 The documentation shall have a space to indicate when and how the deficiencies were corrected.
19.4.10 All documentation shall be maintained and made available for review by the AHJ.
19.4.11 Periodic inspections and testing of a combination fire/smoke damper shall also meet the inspection and testing requirements contained in Chapter 6 of NFPA 105, Standard for Smoke Door Assemblies and Other Opening Protectives.




Findings:

During record review and interview with Staff on 5/12/26, the HVAC damper testing/service records were requested for review.

At 1:16 p.m., the fire/smoke damper testing records were requested.  The facility provided a document dated 8/21/25 that indicated their vendor cycled all the fire dampers in the facility. The documentation did not indicate the location of the dampers in the facility. Upon interview, the Nurse manager stated that they would contact the vendor to see if they had additional inspection documentation. The facility was given until 10:00 a.m. on 5/13/26 to provide the fire damper testing documentation to the California Department of Public Health (CDPH).

 

At 10:00 a.m. on 5/13/26, CDPH did not receive the fire damper testing documentation from the facility.