Department of Health & Human Services

Centers for Medicare & Medicaid Services
Form Approved

OMB No. 0938-0391

Statement of Deficiencies (X1) Provider/Supplier/CLIA Identification Number 55C0001059 (X3) Date Survey Completed 04/10/2019
Name of Provider or Supplier Fort Sutter Surgery Center, A Ca Limited Partnership Street Address, City, State 2801 K Street, Suite 525, Sacramento, CA
For information on the provider's plan to correct this deficiency, please contact the provider or the state survey agency.
(X4) ID Prefix Tag Summary Statement of Deficiencies

(Each deficiency should be preceded by full regulatory or LSC identifying information)
K0355 Portable Fire Extinguishers
CFR(s): NFPA 101

Portable Fire Extinguishers Portable fire extinguishers are selected, installed, inspected, and maintained in accordance with NFPA 10, Standard for Portable Fire Extinguishers. 20.3.5.3, 21.3.5.3, 9.7.4.1, NFPA 10


This STANDARD is not met as evidenced by:
Based on observation and interview, the facility failed to maintain the portable fire extinguishers. This was evidenced by an obstructed extinguisher. This affected all patients, and could result in the inability to locate and/or obtain the extinguisher in the event of a fire.



NFPA 101 Life Safety Code, 2012 edition

21.3.5.3 Portable fire extinguishers shall be provided in ambulatory

health care facilities in accordance with 9.7.4.1.



9.7.4.1* Where required by the provisions of another section

of this Code, portable fire extinguishers shall be selected, installed,

inspected, and maintained in accordance with

NFPA 10, Standard for Portable Fire Extinguishers.



NFPA 10, Standard for Portable Extinguishers, 2010 Edition.

6.1.3.3.1 Fire extinguishers shall not be obstructed or obscured from view.



Findings:



During a tour of the facility and interview with staff on 4/10/19, the portable fire extinguishers were observed.



At 12:50 p.m., the portable fire extinguisher located in Operating Room (OR) 5 was observed. The fire extinguisher was located inside a recessed wall cabinet, and was obstructed from view and access by wheeled medical equipment that were stored directly in front of the fire extinguisher. Upon interview, Staff 2 confirmed the finding.