K0346 Fire Alarm System - Out of Service
CFR(s): NFPA 101

Fire Alarm - Out of Service Fire alarms that are out of service for 4 hours in a 24 hour period, the authority having jurisdiction shall be notified, and the building shall be evacuated or an approved fire watch shall be provided for all parties left unprotected by the shutdown until the fire alarm system has been returned to service. 9.6.1.6


This STANDARD is not met as evidenced by:
Based on document review and interview, the facility failed to maintain interim fire measures. This was evidenced by the failure to provide written protocol to ensure that if the automatic fire alarm system was out of service for more than 4 hours in a 24 hour period, the authority having jurisdiction (AHJ) would be notified. This affected all patients, and could potentially result in the AHJ being unable to exercise oversight in a timely manner if the fire alarm system should become inoperable.



Findings:



During document review and interview with staff on 4/10/19, the interim fire measures and policy were reviewed.



At 11:00 a.m., the approved Fire Watch policy, did not include guidance for notification to the Department of Public Health if the fire alarm system was out of service for more than 4 hours in a 24 hour period. Upon interview, Staff 1 confirmed the finding.