K0353 Sprinkler System - Maintenance and Testing
CFR(s): NFPA 101

Sprinkler System - Maintenance and Testing Automatic sprinkler and standpipe systems are inspected, tested, and maintained in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintaining of Water-based Fire Protection Systems. Records of system design, maintenance, inspection and testing are maintained in a secure location and readily available. a) Date sprinkler system last checked _____________________ b) Who provided system test ____________________________ c) Water system supply source __________________________ Provide in REMARKS information on coverage for any non-required or partial automatic sprinkler system. 9.7.5, 9.7.7, 9.7.8, and NFPA 25


This STANDARD is not met as evidenced by:
.



Based on observation and interview, the facility failed to maintain the automatic sprinkler system per the requirements of:



2012 NFPA 101, 9.7.5

2011 NFPA 25, 5.2.2.2



Findings include:



On 09/17/2019, during a tour of the facility from 10:30 am to 4:30 pm, the surveyor observed a supply air duct coil (external load) resting on the automatic sprinkler pipe above the ceiling near beds 2 and 3 in the existing recovery area.



A member of the maintenance staff was present when this deficiency was identified.



.