K0351 Sprinkler System - Installation
CFR(s): NFPA 101

Sprinkler System - Installation Sprinkler systems (if installed) are installed per NFPA 13. Where more than two sprinklers are installed in a single area for protection, waterflow devices shall be provided to sound the building fire alarm system or to notify a constantly attended location such as a PBX, security office, or emergency room. 20.3.5.1, 20.3.5.2, 21.3.5.1, 21.3.5.2, 9.7.1.2, 9.7, NFPA 13


This STANDARD is not met as evidenced by:
.





Based on observation, the facility failed to provide an electronic supervising (tamper switch) for the backflow preventer valve for the automatic sprinkler system per the requirements of:





2012 NFPA 101, 21.3.5.1, and 9.7.2.1


2010 NFPA 72, 10.7.4, and 10.16.2





This deficiency affects the entire sprinkler system.





Findings include:





During a tour of the facility, the surveyor observed the backflow preventer valve for the automatic sprinkler system did not have an electronic supervising device (tamper switch) installed.





A member of the maintenance staff and the administrator were present, when this deficiency was identified.





.